Fujitsu AIRSTAGE J-IIIL Design & Technical Manual page 528

Table of Contents

Advertisement

¢ Maximum connectable unit numbers in 1 VRF network system
 Controller
• Central controller
Exterior
NOTES:
• *1: Different VRF series may be connected for each of the 4 VRF networks supported by the
product, but different series may not coexist within the same network. (VR-II, V-II, J-II, J-IIS,
and J-IIIL can exist together in same network. V and S can exist together in same network,
too.)
• *2: For 1 VRF network system, total number of Touch panel controller, Central remote con-
troller, Network convertor for Group remote controller, KNX convertor for VRF, Modbus con-
vertor for VRF, BACnet gateway (Hardware) is 16, including 1 Network convertors for Lon-
Works.
• *3: When Group remote controller is used, Network convertor (UTY-VGGXZ1) is required.
1-2. VRF network system
Outdoor unit
Indoor unit
Part name
Model name
System
UTY-APGXZ1
1
controller*
System
UTY-ALGXZ1
controller lite
Touch panel
UTY-DTGYZ1
controller
Central remote
UTY-DCGY
controller
Central remote
UTY-DCGYZ1
controller
Max.
VRF
connectable
network
number
system
1
4
1
1
2
16*
2
16*
2
16*
- (06-6) -
100
400
Max. controllable number
Remote
Indoor
controller
unit
group
1,600 per VRF network
system
400
400
100
100
100
1. System design
Group
16
50