¢ System diagrams
• Multiple remote control
Up to 4 remote controllers can be used to operate the indoor units.
I.U.
A
Master
A, B, C, D: Remote controller cable (For details of controller cable specifications, refer to
troller cable"
in Chapter 6. SYSTEM DESIGN on page 06-62.)
A ≤ 1,640 ft (500 m), A + B ≤ 1,640 ft (500 m), A + B + C ≤ 1,640 ft (500 m), A + B + C + D ≤ 1,640
ft (500 m)
NOTE: Multiple installation method described above is prohibited to combine with 3-wired type re-
mote controller (UTY-RNKU, UTY-RSKU, or UTY-RHKU) and 2-wired type remote con-
troller (UTY-RNRUZ)
• Group control
With a single remote controller, up to 16 indoor units can be simultaneously operated.
A, B, C, D, E: Remote controller cable (For details of controller cable specifications, refer to
troller cable"
in Chapter 6. SYSTEM DESIGN on page 06-62.)
A + B + C + D + E ≤ 1,640 ft (500 m)
2-6. Wired remote controller (Touch panel: UTY-RNRUZ)
I.U.
A
B
A
Master
Slave
Master
I.U.
I.U.
B
C
A
Master
- (05-57) -
I.U.
I.U.
B
C
A
Slave
Slave
Master
I.U.
I.U.
D
E
B
C
D
Slave
Slave
Slave
"Con-
"Con-
2. Control units