Manual Address Setting Method - Fujitsu AIRSTAGE J-IIIL Design & Technical Manual

Table of Contents

Advertisement

1-3. Manual address setting method

¢ Address setting description
• Refrigerant circuit address (Set A and Set D)
When there are 2 or more refrigerant systems in one VRF network system, an exclusive refrig-
erant circuit address should be set for each refrigerant system.
Refrigerant system: One refrigerant circuit which has connected between outdoor unit and in-
door unit by piping.
Refrigerant system 1
01
01
00
0
01
• Setting example
Refrigerant circuit
address
01
11
25
50
– Setting range: 00—99 (Arbitrary numbers can be set.)
– Same address should be set in all the indoor unit and outdoor unit in the same refrigerant
circuit.
1-3. Manual address setting method
01
1
01
02
2
02
00
Outdoor unit (Set A)
Rotary switch setting
REF AD x10
0
1
2
5
Refrigerant system 2
02
0
02
01
1
02
02
2
REF AD x1
1
1
5
0
- (07-8) -
Refrigerant system 25
25
25
00
0
25
01
1
Indoor unit (Set D)
Rotary switch setting
REF AD x10
REF AD x1
0
1
2
5
25
02
2
1
1
5
0
1. System settings