Fujitsu AIRSTAGE J-IIIL Design & Technical Manual page 808

Table of Contents

Advertisement

• Outdoor temperature zone
B + 3.6°F (2°C): 46.4°F (8°C)
A + 3.6°F (2°C): -0.4°F (-18°C)
*: Adjustable by function setting 36 and 37 for outdoor unit
• Operation status
Outdoor temperature
Outdoor temperature zone *
Fan
* The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min.
NOTE: • In following operations, EEV will be on in heat pump prohibition zone.
– Other than heating
– Test run
• This control is enabled when the function setting number 35 of the outdoor unit (presence
of heater selection control by outdoor temperature) is enabled.
3-3. External output
Outdoor temp.
Heater only zone  
 
B: 42.8°F (6°C)*
Combination zone
  (Heat pump + Heater)
A: -4°F (-20°C)*
Heater only zone
 
46.4°F (8°C)
42.8°F (6°C)
(Factory setting)
-0.4°F (-18°C)
-4°F (-20°C)
On
EEV On/Off
Off
12 V
Heater
0 V
On
DIP-SW2-3 On
Off
On
DIP-SW2-3 Off
Off
 
 
Heat pump prohibition zone
Combination zone
- (08-54) -
3. Indoor unit