Generic control point (16 pcs) SPCGAPC
Function block
GUID-3A7D9472-39BF-4522-83CA-89BFBA1800E6 V1 EN
Figure 97:
Function block
Functionality
The generic control point (16 pcs) function SPCGAPC can be used in combination
with other function blocks such as FKEYGGIO. SPCGAPC offers the capability to
activate its outputs through a local or remote control. The local control is provided
through the buttons in the front panel and the remote control is provided through
communications. SPCGAPC has two modes of operation. In the "Toggle" mode, the
block toggles the output signal for every input pulse received. In the "Pulsed" mode,
the block generates an output pulse of a preset duration.
For example, if the Operation mode is "Toggle", the output O# is initially "False". The
rising edge in IN# sets O# to "True". The falling edge of IN# has no effect. Next rising
edge of IN# sets O# to "False".
GUID-F0078144-A40B-4A72-915A-0E6665F8DEB1 V1 EN
Figure 98:
Operation in "Toggle" mode
From the remote communication point of view SPCGAPC toggled
operation mode is always working as persistent mode. The output O#
follows the value written to the input IN#.