1MRS757644 F
4.3.2.7
620 series
Technical Manual
GUID-5E0D15BA-ADA9-4FE0-A85D-5C6E86D7E32B V2 EN
Figure 274:
Alternative connection example of current transformers of Type 2
The CT secondary currents often differ from the rated current at the rated load of the
power transformer. The CT transforming ratios can be corrected on both sides of the
power transformer with the CT ratio Cor Wnd 1 and CT ratio Cor Wnd 2 settings.
Signals
Table 484:
TR2PTDF Input signals
Name
Type
I_A1
SIGNAL
I_B1
SIGNAL
I_C1
SIGNAL
I_A2
SIGNAL
I_B2
SIGNAL
I_C2
SIGNAL
Table continues on next page
Protection functions
Default
Description
0
Phase A primary current
0
Phase B primary current
0
Phase C primary current
0
Phase A secondary current
0
Phase B secondary current
0
Phase C secondary current
Section 4