Section 4
Protection functions
784
GUID-C448B20B-4253-4F41-BB8A-ADA6A8E59CE3 V1 EN
Figure 401:
Functional module diagram
Natural unbalance Compensation
A standard double-Y-connected shunt capacitor bank configuration is shown in
Figure
402. The fundamental frequency component of an unbalance current is
measured on the common neutral connecting the two balanced parts of a shunt
capacitor bank, that is, between star point 1 and star point 2.
GUID-B90CC18A-3603-4485-8ED0-43C37A035522 V1 EN
Figure 402:
Double-Y-connected capacitor bank
The phase angle of the measured fundamental frequency component of the unbalance
current I_UNB is synchronized by using the phase current I_A as a reference.
_
I
I UNB
= ∠
− ∠
unb
GUID-CB8F2C7C-9CAC-47D7-A33F-C6369E34EC7B V1 EN
_
I A
1MRS757644 F
(Equation 146)
620 series
Technical Manual