Section 4
Protection functions
4.8.1.6
4.8.1.7
Table 694:
DUPPDPR Group settings (Basic)
Parameter
Start value
Operate delay time
Table 695:
DUPPDPR Non group settings (Basic)
Parameter
Operation
732
Signals
Table 692:
DUPPDPR Input signals
Name
I_A
I_B
I_C
I
1
U_A_AB
U_B_BC
U_C_CA
U
1
DISABLE
BLOCK
Table 693:
DUPPDPR Output signals
Name
OPERATE
START
Settings
Values (Range)
Unit
0.01...2.00
xSn
40...300000
ms
Values (Range)
Unit
1=on
5=off
Type
Default
Description
SIGNAL
0
Phase A current
SIGNAL
0
Phase B current
SIGNAL
0
Phase C current
SIGNAL
0
Positive sequence current
SIGNAL
0
Phase-to-earth voltage A or phase-to-phase
voltage AB
SIGNAL
0
Phase-to-earth voltage B or phase-to-phase
voltage BC
SIGNAL
0
Phase-to-earth voltage C or phase-to-phase
voltage CA
SIGNAL
0
Positive phase sequence voltage
BOOLEAN
0=False
Signal to block the function during generator
startup
BOOLEAN
0=False
Block signal for activating the blocking mode
Type
Description
BOOLEAN
Operate
BOOLEAN
Start
Step
Default
0.01
0.10
10
40
Step
Default
1=on
1MRS757644 F
Description
Start value
Operate delay time
Description
Operation On/Off
Technical Manual
620 series