1MRS757644 F
Table 696:
DUPPDPR Non group settings (Advanced)
Parameter
Values (Range)
Measurement mode
Reset delay time
Pol reversal
Disable time
4.8.1.8
4.8.1.9
620 series
Technical Manual
Unit
1=PhsA, PhsB,
PhsC
2=Arone
3=Pos Seq
4=PhsAB
5=PhsBC
6=PhsCA
7=PhsA
8=PhsB
9=PhsC
0...60000
ms
0=False
1=True
0...60000
ms
Monitored data
Table 697:
DUPPDPR Monitored data
Name
START_DUR
P
Q
S
PF_ANGLE
DUPPDPR
Technical data
Table 698:
DUPPDPR Technical data
Characteristic
1)
Operation accuracy
2)3)
Start time
Reset time
Table continues on next page
Step
Default
3=Pos Seq
10
20
0=False
1000
0
Type
Values (Range)
FLOAT32
0.00...100.00
FLOAT32
-160.000...160.0
00
FLOAT32
-160.000...160.0
00
FLOAT32
0.000...160.000
FLOAT32
-180.00...180.00
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
Depending on the frequency of the measured
current and voltage:
f
Power measurement accuracy ±3% of the set
value or ±0.002 × S
Phase angle: ±2°
Typically 45 ms
Typically 30 ms
Protection functions
Description
Selection of power calculation method
Reset delay time
Reverse the definition of the power
direction
Additional wait time after CB closing
Unit
Description
%
Ratio of start time /
operate time
xSn
Active power
xSn
Reactive power
xSn
Apparent power
deg
Power factor angle
Status
±2 Hz
n
n
Section 4
733