ABB RELION 620 Series Technical Manual page 951

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MRS757644 F
8.1.6.2
8.1.6.3
8.1.6.4
Table 908:
VAMMXU Non group settings (Basic)
Parameter
Values (Range)
Operation
V high high limit
V high limit
V low limit
V low low limit
V deadband
Table 909:
VAMMXU Non group settings (Advanced)
Parameter
Values (Range)
Measurement mode
620 series
Technical Manual
Function block
GUID-283FF4B3-BB34-471B-9ADF-0015C67DED72 V1 EN
Figure 493:
Function block symbol
Signals
Table 906:
VAMMXU Input signals
Name
U_A_AB
BLOCK
Table 907:
VAMMXU Output signals
Name
HIGH_ALARM
HIGH_WARN
LOW_WARN
LOW_ALARM
Settings
Unit
1=on
5=off
0.00...4.00
xUn
0.00...4.00
xUn
0.00...4.00
xUn
0.00...4.00
xUn
100...100000
Unit
1=RMS
2=DFT
Type
Default
Description
SIGNAL
0
Phase-to-earth voltage A or phase-to-phase
voltage AB
BOOLEAN
0=False
Block signal for all binary outputs
Type
Description
BOOLEAN
High alarm
BOOLEAN
High warning
BOOLEAN
Low warning
BOOLEAN
Low alarm
Step
Default
1=on
1
1.40
1
1.20
1
0.00
1
0.00
1
10000
Step
Default
2=DFT
Section 8
Measurement functions
Description
Operation Off / On
High alarm voltage limit
High warning voltage limit
Low warning voltage limit
Low alarm voltage limit
Deadband configuration value for integral
calculation. (percentage of difference
between min and max as 0,001 % s)
Description
Selects used measurement mode
945