1MRS757644 F
3.14.4.4
3.14.4.5
Table 70:
RESTVTR Non group settings (Basic)
Parameter
Values (Range)
Primary voltage
Secondary voltage
Amplitude Corr
Angle correction
3.14.4.6
620 series
Technical Manual
ALARM is activated when two or more consecutive SMV frames are lost or late. A
single loss of frame is corrected with a zero-order hold scheme. In this case, the effect
on protection is considered negligible and the WARNING or ALARM outputs are not
activated. The output is held on for 10 seconds after the conditions return to normal.
The SMV Max Delay parameter defines how long the receiver waits for the SMV
frames before activating the ALARM output. This parameter can be accessed via
Configuration/System/Common. Waiting of the SMV frames also delays the local
measurements of the receiver to keep them correctly time aligned. The SMV Max
Delay values include sampling, processing and network delay.
The WARNING output in the receiver is activated if the synchronization accuracy of
the sender or the receiver is worse than 4 μs. The output is held on for 10 seconds after
the synchronization accuracy returns within limits.
The WARNING output is always internally active whenever the ALARM output is
active.

Signals

Table 68:
RESTVTR Input signals
Name
Uo
Table 69:
RESTVTR Output signals
Name
ALARM
WARNING

Settings

Unit
0.100...440.000
kV
60...210
V
0.9000...1.1000
-20.0000...20.0000
deg

Monitored data

Monitored data is available in three locations.
Type
Default
INT32-UL0
0
Type
Description
BOOLEAN
Alarm
BOOLEAN
Warning
Step
Default
0.001
11.547
1
100
0.0001
1.0000
0.0001
0.0000
Section 3
Basic functions
Description
IEC61850-9-2 residual
voltage
Description
Primary voltage
Secondary voltage
Amplitude correction
Angle correction factor
131