ABB RELION 620 Series Technical Manual page 73

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MRS757644 F
Parameter
Values (Range)
Class1OvInfNo
Class1OvBackOff
GI Optimize
DR Notification
Block Monitoring
Internal Overflow
EC_FRZ
Table 20:
IEC 61850-8-1 MMS settings
Parameter
Values (Range)
Unit mode
1) MMS client expects primary values from event reporting and data attribute reads
2) MMS client expects nominal values from event reporting and data attribute reads; this is the default for PCM600
3) For PCM600 use only, When Unit mode is set to "Primary", the PCM600 client can force its session to "Nominal" by selecting "Primary-
Nominal" and thus parameterizing in native form. The selection is not stored and is therefore effective only for one session. This value has
no effect if selected via the LHMI.
Table 21:
Modbus settings
Parameter
Values (Range)
Operation
Port
Mapping selection
Address
Link mode
TCP port
Parity
Table continues on next page
620 series
Technical Manual
Unit
0...255
0...500
0=Standard
behaviour
1=Skip
spontaneous
2=Only overflown
3=Combined
0=False
1=True
0=Not in use
1=Discard events
2=Keep events
0=False
1=True
0=False
1=True
Unit
1)
1=Primary
2)
0=Nominal
2=Primary-
3)
Nominal
Unit
1=on
5=off
1=COM 1
2=COM 2
3=Ethernet - TCP 1
1...2
1...254
1=RTU
2=ASCII
1...65535
0=none
1=odd
2=even
Step
Default
1
255
1
500
0=Standard
behaviour
0=False
0=Not in use
0=False
0=False
Step
Default
0=Nominal
Step
Default
5=off
3=Ethernet - TCP
1
1
1
1
1
1=RTU
1
502
2=even
Section 3
Basic functions
Description
Information Number for Class 1 overflow
indication
Backoff Range for Class1 buffer
Optimize GI traffic
Disturbance Recorder spontaneous
indications enabled/disabled
Blocking of Monitoring Direction
Internal Overflow: TRUE-System level
overflow occured (indication only)
Control point for freezing energy counters
Description
IEC 61850-8-1 unit mode
Description
Enable or disable this protocol instance
Port selection for this protocol instance.
Select between serial and Ethernet based
communication.
Chooses which mapping scheme will be
used for this protocol instance.
Unit address
Selects between ASCII and RTU mode.
For TCP, this should always be RTU.
Defines the listening port for the Modbus
TCP server. Default = 502.
Parity for the serial connection.
67