ABB RELION 620 Series Technical Manual page 403

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MRS757644 F
4.2.2.11
Table 414:
DEFLPDEF Group settings (Basic)
Parameter
Values (Range)
Start value
Start value Mult
Directional mode
Time multiplier
Operating curve type
Operate delay time
Characteristic angle
Max forward angle
Max reverse angle
Min forward angle
Min reverse angle
Voltage start value
620 series
Technical Manual
Table 412:
DEFLPDEF Output signals
Name
OPERATE
START
Table 413:
DEFHPDEF Output signals
Name
OPERATE
START
Settings
Unit
0.010...5.000
xIn
0.8...10.0
1=Non-directional
2=Forward
3=Reverse
0.05...15.00
1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
50...200000
ms
-179...180
deg
0...180
deg
0...180
deg
0...180
deg
0...180
deg
0.010...1.000
xUn
Type
Description
BOOLEAN
Operate
BOOLEAN
Start
Type
Description
BOOLEAN
Operate
BOOLEAN
Start
Step
Default
0.005
0.010
0.1
1.0
2=Forward
0.01
1.00
15=IEC Def. Time
10
50
1
-90
1
80
1
80
1
80
1
80
0.001
0.010
Section 4
Protection functions
Description
Start value
Multiplier for scaling the start value
Directional mode
Time multiplier in IEC/ANSI IDMT curves
Selection of time delay curve type
Operate delay time
Characteristic angle
Maximum phase angle in forward
direction
Maximum phase angle in reverse
direction
Minimum phase angle in forward direction
Minimum phase angle in reverse direction
Voltage start value
397

Hide quick links:

Advertisement

Table of Contents
loading