Monitored Data; Technical Data; Technical Revision History - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MRS757644 F
Table 345:
JAMPTOC Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
4.1.8.8
4.1.8.9
4.1.8.10
620 series
Technical Manual
Unit
0...60000
ms

Monitored data

Table 346:
JAMPTOC Monitored data
Name
START
START_DUR
JAMPTOC

Technical data

Table 347:
JAMPTOC Technical data
Characteristic
Operation accuracy
Reset time
Reset ratio
Retardation time
Operate time accuracy in definite time mode

Technical revision history

Table 348:
JAMPTOC Technical revision history
Technical revision
B
C
Step
Default
1
100
Type
Values (Range)
BOOLEAN
0=False
1=True
FLOAT32
0.00...100.00
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
Depending on the frequency of the measured
current: f
±1.5% of the set value or ±0.002 × I
Typically 40 ms
Typically 0.96
<35 ms
±1.0% of the set value or ±20 ms
Change
Internal improvement
Internal improvement
Section 4
Protection functions
Description
Reset delay time
Unit
Description
Start
%
Ratio of start time /
operate time
Status
±2 Hz
n
n
337