ABB RELION 620 Series Technical Manual page 978

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 8
Measurement functions
972
Table 950:
RDRE Non-group binary channel settings
Parameter
Values (Range) Unit
Operation
1=on
5=off
Level trigger
1=Positive or
mode
Rising
2=Negative or
Falling
3=Both
4=Level
trigger off
Storage mode
0=Waveform
1=Trend /
cycle
Channel id
0 to 64
text
characters,
alphanumeric
Table 951:
RDRE Control data
Parameter
Values (Range) Unit
Trig recording
0=Cancel
1=Trig
Clear
0=Cancel
recordings
1=Clear
Step
Default
1
5=off
1
1=Rising
1
0
DR binary
channel X
Step
Default
1MRS757644 F
Description
Binary
channel is
enabled or
disabled
Level trigger
mode for the
binary
channel
Storage mode
for the binary
channel
Identification
text for the
analog
channel used
in the
COMTRADE
format
Description
Trigger the
disturbance
recording
Clear all
recordings
currently in
memory
620 series
Technical Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents