1MRS757644 F
4.3.1.6
4.3.1.7
Table 478:
MPDIF Group settings (Basic)
Parameter
Values (Range)
Low operate value
High operate value
Slope section 2
End section 1
End section 2
Table 479:
MPDIF Group settings (Advanced)
Parameter
Values (Range)
Slope section 3
DC restrain enable
620 series
Technical Manual
Signals
Table 476:
MPDIF Input signals
Name
I_A1
I_B1
I_C1
I_A2
I_B2
I_C2
BLOCK
BLK_OPR_LS
BLK_OPR_HS
Table 477:
MPDIF Output signals
Name
OPERATE
OPR_LS
OPR_HS
INT_BLKD
Settings
Unit
5...30
%Ir
100...1000
%Ir
10...50
%
0...100
%Ir
100...300
%Ir
Unit
10...100
%
0=False
1=True
Type
Default
Description
Signal
0
Phase A primary current
Signal
0
Phase B primary current
Signal
0
Phase C primary current
Signal
0
Phase A secondary current
Signal
0
Phase B secondary current
Signal
0
Phase C secondary current
BOOLEAN
0=False
Block signal for activating the blocking mode
BOOLEAN
0=False
Blocks operate outputs from biased stage
BOOLEAN
0=False
Blocks operate outputs from instantaneous stage
Type
Description
BOOLEAN
Operate
BOOLEAN
Operate from low set
BOOLEAN
Operate from high set
BOOLEAN
Internal block status
Step
Default
1
5
10
500
1
30
1
50
1
150
Step
Default
1
100
0=False
Section 4
Protection functions
Description
Basic setting for the stabilized stage start
Instantaneous stage operate value
Slope of the second line of the operating
characteristics
Turn-point between the first and the
second line of the operating
characteristics
Turn-point between the second and the
third line of the operating characteristics
Description
Slope of the third line of the operating
characteristics
Setting for enabling DC restrain feature
505