ABB RELION 620 Series Technical Manual page 71

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MRS757644 F
Table 18:
HMI settings
Parameter
Values (Range)
FB naming convention
Default view
Backlight timeout
Web HMI mode
Web HMI timeout
SLD symbol format
Autoscroll delay
Setting visibility
Table 19:
IEC 60870-5-103 settings
Parameter
Values (Range)
Operation
Serial port
Address
Start delay
End delay
DevFunType
UsrFunType
UsrInfNo
Class1Priority
Class2Interval
Table continues on next page
620 series
Technical Manual
Unit
1=IEC61850
2=IEC60617
3=IEC-ANSI
1=Measurements
2=Main menu
3=SLD
1...60
min
1=Active read only
2=Active
3=Disabled
1...60
min
1=IEC
2=ANSI
0...30
s
1=Basic
2=Advanced
Unit
1=on
5=off
1=COM 1
2=COM 2
1...255
0...20
char
0...20
char
0...255
0...255
0...255
0=Ev High
1=Ev/DR Equal
2=DR High
0...86400
s
Step
Default
1=IEC61850
1=Measurements
1
3
3=Disabled
1
3
1=IEC
1
0
1=Basic
Step
Default
5=off
1=COM 1
1
1
1
4
1
4
1
9
1
10
1
230
0=Ev High
1
30
Section 3
Basic functions
Description
FB naming convention used in IED
LHMI default view
LHMI backlight timeout
Web HMI functionality
Web HMI login timeout
Single Line Diagram symbol format
Autoscroll delay for Measurements view
Setting visibility for HMI
Description
Selects if this protocol instance is enabled
or disabled
COM port
Unit address
Start frame delay in chars
End frame delay in chars
Device Function Type
Function type for User Class 2 Frame
Information Number for User Class2
Frame
Class 1 data sending priority relationship
between Events and Disturbance
Recorder data.
Interval in seconds to send class 2
response
65

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents