Signals - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MRS757644 F
4.1.7.6
620 series
Technical Manual
Table 332:
Conversion table between one and two time constants
Short time constant (min) Long time constant (min) Weighting factor p
Single time constant
(min)
10
1.1
15
1.6
20
2.1
25
2.6
30
3.1
35
3.6
40
4.1
45
4.8
50
5.1
55
5.6
60
6.1
65
6.7
70
7.2
75
7.8
The default Max temperature setting is 105°C. This value is chosen since even though
the IEC 60076-7 standard recommends 98°C as the maximum allowable temperature
in long-time loading, the standard also states that a transformer can withstand the
emergency loading for weeks or even months, which may produce the winding
temperature of 140°C. Therefore, 105°C is a safe maximum temperature value for a
transformer if the Max temperature setting value is not given by the transformer
manufacturer.

Signals

Table 333:
T2PTTR Input signals
Name
Type
I_A
SIGNAL
I_B
SIGNAL
I_C
SIGNAL
BLOCK
BOOLEAN
AMB_TEMP
FLOAT32
Table 334:
T2PTTR Output signals
Name
Type
OPERATE
BOOLEAN
START
BOOLEAN
ALARM
BOOLEAN
BLK_CLOSE
BOOLEAN
Protection functions
17
25
33
41
49
58
60
75
82
90
98
107
115
124
Default
Description
0
Phase A current
0
Phase B current
0
Phase C current
0=False
Block signal for activating the blocking mode
0
The ambient temperature used in the calculation
Description
Operate
Start
Thermal Alarm
Thermal overload indicator. To inhibite reclose.
Section 4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
331