1MRS757644 F
620 series
Technical Manual
s2
GUID-367BDBC9-D2E8-48D3-B98F-623F7CD70D99 V3 EN
Figure 287:
Connection scheme for the restricted earth-fault protection according
to the high-impedance principle
High-impedance principle
High-impedance principle is stable for all types of faults outside the zone of
protection. The stabilization is obtained by a stabilizing resistor in the differential
circuit. This method requires that all the CTs used have a similar magnetizing
characteristic, same ratio and relatively high knee point voltage. CTs on each sides are
connected in parallel along with a relay-measuring branch as shown in
The measuring branch is a series connection of stabilizing resistor and IED.
s1
VDR
Stabilizing
Resistor
High impedance
protection
(HREFPDIF)
Section 4
Protection functions
s1
s2
Figure
288.
561