GOOSERCV_ENUM function block does not receive the value from the sending
device or it is invalid, the default value (0) is used and the ALARM is activated in the
T_HEALTH function block.

Signals

Table 85:
T_HEALTH Input signals
Name
Type
IN1
Any
Table 86:
T_HEALTH Output signals
Name
Type
OK
BOOLEAN
WARNING
BOOLEAN
ALARM
BOOLEAN

T_F32_INT8 function block

Function block

GUID-F0F44FBF-FB56-4BC2-B421-F1A7924E6B8C V1 EN
Figure 58:
Function block

Functionality

The T_F32_INT8 function is used to convert 32-bit floating type values to 8-bit
integer type. The rounding operation is included. Output value saturates if the input
value is below the minimum or above the maximum value. .
Signals
Table 87:
T_F32_INT8 Input signals
Name
Type
F32
FLOAT32
Table 88:
T_F32_INT8 Output signal
Name
INT8
Default
0
Description
Output signal
Output signal
Output signal
Default
0.0
Type
INT8
Section 3
Basic functions
Description
Input signal
Description
Input signal
Description
Output signal