Minimum Pulse Timer Tpsgapc - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MRS757644 F
3.17.2.2
Table 149:
TPSGAPC Non group settings (Basic)
Parameter
Values (Range)
Pulse time
620 series
Technical Manual

Minimum pulse timer TPSGAPC

Function block
GUID-F9AACAF7-2183-4315-BE6F-CD53618009C0 V1 EN
Figure 78:
Function block
Functionality
The Minimum second pulse timer function TPSGAPC contains two independent
timers. The function has a settable pulse length (in seconds). The timers are used for
setting the minimum pulse length for example, the signal outputs. Once the input is
activated, the output is set for a specific duration using the Pulse time setting. Both
timers use the same setting parameter.
GUID-8196EE39-3529-46DC-A161-B1C40224559F V1 EN
Figure 79:
A = Trip pulse is shorter than Pulse time setting, B = Trip pulse is
longer than Pulse time setting
Signals
Table 147:
TPSGAPC Input signals
Name
IN1
IN2
Table 148:
TPSGAPC Output signals
Name
OUT1
OUT2
Settings
Unit
0...300
s
Type
Default
Description
BOOLEAN
0=False
Input 1
BOOLEAN
0=False
Input 2
Type
Description
BOOLEAN
Output 1 status
BOOLEAN
Output 2 status
Step
Default
1
0
Section 3
Basic functions
Description
Minimum pulse time
161