1MRS757644 F
620 series
Technical Manual
Connection of current transformers
The connections of the primary current transformers are designated as Type 1 and
Type 2.
If the positive directions of the winding 1 and winding 2 protection relay currents
are opposite, the CT connection type is of "Type 1". The connection examples of
"Type 1" are as shown in figures
If the positive directions of the winding 1 and winding 2 protection relay currents
equate, the CT connection type setting parameter is "Type 2". The connection
examples of "Type 2" are as shown in figures
The default value of the CT connection type setting is "Type 1".
GUID-A6716146-6ECD-46A2-B2AC-4408DDDB7BF6 V2 EN
Figure 250:
Connection of current transformer of Type 1, example 1
Protection functions
250
and 251.
252
and 253.
Section 4
501