Section 4
Protection functions
4.10.6
4.10.7
Table 723:
STTPMSU Group settings (Basic)
Parameter
Motor start-up A
Motor start-up time
Lock rotor time
Str over delay time
Table 724:
STTPMSU Group settings (Advanced)
Parameter
Start detection A
766
Signals
Table 721:
STTPMSU Input signals
Name
I_A
I_B
I_C
BLOCK
BLK_LK_ST
CB_CLOSED
STALL_IND
ST_EMERG_ENA
Table 722:
STTPMSU Output signals
Name
OPR_IIT
OPR_STALL
MOT_START
LOCK_START
Settings
Values (Range)
Unit
1.0...10.0
xIn
1...80
s
2...120
s
0...60000
ms
Values (Range)
Unit
0.1...10.0
xIn
Type
Default
Description
SIGNAL
0
Phase A current
SIGNAL
0
Phase B current
SIGNAL
0
Phase C current
BOOLEAN
0=False
Block of function
BOOLEAN
0=False
Blocks lock out condition for restart of motor
BOOLEAN
0=False
Input showing the status of motor circuit breaker
BOOLEAN
0=False
Input signal for showing the motor is not stalling
BOOLEAN
0=False
Enable emergency start to disable lock of start of
motor
Type
Description
BOOLEAN
Operate/trip signal for thermal stress.
BOOLEAN
Operate/trip signal for stalling protection.
BOOLEAN
Signal to show that motor startup is in progress
BOOLEAN
Lock out condition for restart of motor.
Step
Default
0.1
2.0
1
5
1
10
1
100
Step
Default
0.1
1.5
1MRS757644 F
Description
Motor starting current
Motor starting time
Permitted stalling time
Time delay to check for completion of
motor startup period
Description
Current value for detecting starting of
motor.
Technical Manual
620 series

Hide quick links: