Section 4
Protection functions
644
Table 592:
Reset time functionality when IDMT operation time curve selected
Reset functionality
Instantaneous
Operation timer is
reset
"Reset
instantaneously"
when drop-off
occurs
Frozen timer
Operation timer is
frozen during
drop-off
Linear decrease
Operation timer
value linearly
decreases during
the drop-off
situation
Setting Type of
Setting Type of time
reset curve
reset
"Immediate"
Setting has no
effect
"Def time reset"
"Freeze Op timer"
"Def time reset"
"Decrease Op
timer"
1MRS757644 F
Setting Reset delay
time
Setting has no
effect
Operate timer is
reset after the set
Reset delay time
has elapsed
Operate timer is
reset after the set
Reset delay time
has elapsed