Section 4
Protection functions
4.5.5.6
4.5.5.7
Table 615:
ROVPTOV Group settings (Basic)
Parameter
Start value
Operate delay time
Table 616:
ROVPTOV Non group settings (Basic)
Parameter
Operation
Uo signal Sel
Table 617:
ROVPTOV Non group settings (Advanced)
Parameter
Reset delay time
660
component. Therefore, this function is often used as a backup protection or as a release
signal for the feeder earth-fault protection.
The protection can also be used for the earth-fault protection of generators and motors
and for the unbalance protection of capacitor banks.
The residual voltage can be calculated internally based on the measurement of the
three-phase voltage. This voltage can also be measured by a single-phase voltage
transformer, located between a transformer star point and earth, or by using an open-
delta connection of three single-phase voltage transformers.
Signals
Table 613:
ROVPTOV Input signals
Name
Uo
BLOCK
Table 614:
ROVPTOV Output signals
Name
OPERATE
START
Settings
Values (Range)
Unit
0.010...1.000
xUn
40...300000
ms
Values (Range)
Unit
1=on
5=off
1=Measured Uo
2=Calculated Uo
Values (Range)
Unit
0...60000
ms
Type
Default
Description
SIGNAL
0
Residual voltage
BOOLEAN
0=False
Block signal for activating the blocking mode
Type
Description
BOOLEAN
Operate
BOOLEAN
Start
Step
Default
0.001
0.030
1
40
Step
Default
1=on
1=Measured Uo
Step
Default
1
20
1MRS757644 F
Description
Residual overvoltage start value
Operate delay time
Description
Operation Off / On
Selection for used Uo signal
Description
Reset delay time
Technical Manual