1MRS757644 F
4.1.3.8
620 series
Technical Manual
direction of the directional functionality. The double arrows define the non-
directional functionality where faults can be detected in both directions.
GUID-276A9D62-BD74-4335-8F20-EC1731B58889 V1 EN
Figure 137:
Closed ring network topology where feeding lines are protected with
directional overcurrent protection relays

Signals

Table 276:
DPHLPDOC Input signals
Name
Type
I_A
SIGNAL
I_B
SIGNAL
I_C
SIGNAL
I
SIGNAL
2
U_A_AB
SIGNAL
U_B_BC
SIGNAL
U_C_CA
SIGNAL
U
SIGNAL
1
U
SIGNAL
2
Table continues on next page
Protection functions
Default
Description
0
Phase A current
0
Phase B current
0
Phase C current
0
Negative phase sequence current
0
Phase-to-earth voltage A or phase-to-phase
voltage AB
0
Phase-to-earth voltage B or phase-to-phase
voltage BC
0
Phase-to-earth voltage C or phase-to-phase
voltage CA
0
Positive phase sequence voltage
0
Negative phase sequence voltage
Section 4
275