Parameter
Values (Range)
Voltage level 4
Voltage level 5
Voltage level 6
Voltage level 7
Voltage level 8
Voltage level 9
Voltage level 10
Recovery time 1
Recovery time 2
Recovery time 3
Recovery time 4
Recovery time 5
Recovery time 6
Recovery time 7
Recovery time 8
Recovery time 9
Recovery time 10
4.5.9.8
620 series
Technical Manual
Unit
0.00...1.20
xUn
0.00...1.20
xUn
0.00...1.20
xUn
0.00...1.20
xUn
0.00...1.20
xUn
0.00...1.20
xUn
0.00...1.20
xUn
0...300000
ms
0...300000
ms
0...300000
ms
0...300000
ms
0...300000
ms
0...300000
ms
0...300000
ms
0...300000
ms
0...300000
ms
0...300000
ms
Monitored data
Table 652:
LVRTPTUV Monitored data
Name
LVRTPTUV
Step
Default
0.01
0.90
0.01
0.90
0.01
0.90
0.01
0.90
0.01
0.90
0.01
0.90
0.01
0.90
1
500
1
1000
1
10000
1
10000
1
10000
1
10000
1
10000
1
10000
1
10000
1
10000
Type
Values (Range)
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Section 4
Protection functions
Description
4th voltage coordinate for defining LVRT
curve
5th voltage coordinate for defining LVRT
curve
6th voltage coordinate for defining LVRT
curve
7th voltage coordinate for defining LVRT
curve
8th voltage coordinate for defining LVRT
curve
9th voltage coordinate for defining LVRT
curve
10th voltage coordinate for defining LVRT
curve
1st time coordinate for defining LVRT
curve
2nd time coordinate for defining LVRT
curve
3rd time coordinate for defining LVRT
curve
4th time coordinate for defining LVRT
curve
5th time coordinate for defining LVRT
curve
6th time coordinate for defining LVRT
curve
7th time coordinate for defining LVRT
curve
8th time coordinate for defining LVRT
curve
9th time coordinate for defining LVRT
curve
10th time coordinate for defining LVRT
curve
Unit
Description
Status
693