ABB RELION 620 Series Technical Manual page 864

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 5
Protection related functions
5.7.6
5.7.7
Table 819:
SCEFRFLO Group settings (Basic)
Parameter
Z Max phase load
Ph leakage Ris
Ph capacitive React
R1 line section A
X1 line section A
Table continues on next page
858
Signals
Table 817:
SCEFRFLO Input signals
Name
I_A
I_B
I_C
Io
I
1
I
2
U_A_AB
U_B_BC
U_C_CA
Uo
U
1
U
2
BLOCK
TRIGG
TRIGG_XC0F
Table 818:
SCEFRFLO Output signals
Name
ALARM
Settings
Values (Range)
Unit
1.0...10000.0
ohm
20...1000000
ohm
10...1000000
ohm
0.000...1000.000
ohm / pu
0.000...1000.000
ohm / pu
Type
Default
Description
SIGNAL
0
Phase A current
SIGNAL
0
Phase B current
SIGNAL
0
Phase C current
SIGNAL
0
Residual current
SIGNAL
0
Positive sequence current
SIGNAL
0
Negative sequence current
SIGNAL
0
Phase to earth voltage A or phase to phase voltage
AB
SIGNAL
0
Phase to earth voltage B or phase to phase voltage
BC
SIGNAL
0
Phase to earth voltage C or phase to phase voltage
CA
SIGNAL
0
Residual voltage
SIGNAL
0
Positive phase sequence voltage
SIGNAL
0
Negative phase sequence voltage
BOOLEAN
0=False
Signal for blocking the triggering
BOOLEAN
0=False
Distance calculation triggering signal
BOOLEAN
0=False
XC0F calculation triggering signal
Type
Description
BOOLEAN
Fault location alarm signal
Step
Default
0.1
80.0
1
210000
1
7000
0.001
1.000
0.001
1.000
1MRS757644 F
Description
Impedance per phase of max. load,
overcurr./under-imp., PSL
Line PhE leakage resistance in primary
ohms
Line PhE capacitive reactance in primary
ohms
Positive sequence line resistance, line
section A
Positive sequence line reactance, line
section A
Technical Manual
620 series

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents