Selection of input signal type

The function module inputs accept current or resistance type signals. The inputs are
configured for a particular type of input type by the channel-specific Input mode
setting. The default value for all inputs is "Not in use", which means that the channel
is not sampled at all, and the output value quality is set accordingly.
Table 52:
Limits for the RTD/mA inputs
Input mode
Description
Not in use
Default selection. Used when the corresponding input is not used.
0...20 mA
Selection for analog DC milliampere current inputs in the input range of 0...20 mA.
Resistance
Selection for RTD inputs in the input range of 0...2000 Ω.
Pt100
Selection for RTD inputs, when temperature sensor is used. All the selectable
Pt250
sensor types have their resistance vs. temperature characteristics stored in the
Ni100
module; default measuring range is -40...200°C.
Ni120
Ni250
Cu10

Selection of output value format

Each input has independent Value unit settings that are used to select the unit for the
channel output. The default value for the Value unit setting is "Dimensionless". Input
minimum and Input maximum, and Value maximum and Value minimum settings have
to be adjusted according to the input channel. The default values for these settings are
set to their maximum and minimum setting values.
When the channel is used for temperature sensor type, set the Value unit setting to
"Degrees celsius". When Value unit is set to "Degrees celsius", the linear scaling is not
possible, but the default range (-40...200 °C) can be set smaller with the Value
maximum and Value minimum settings.
When the channel is used for DC milliampere signal and the application requires a
linear scaling of the input range, the Value unit setting value has to be
"Dimensionless", where the input range can be linearly scaled with settings Input
minimum and Input maximum to Value minimum and Value maximum. When
milliampere is used as an output unit, Value unit has to be "Ampere". When Value unit
is set to "Ampere", the linear scaling is not possible, but the default range (0...20 mA)
can be set smaller with the Value maximum and Value minimum settings.
When the channel is used for resistance type signals and the application requires a
linear scaling of the input range, the Value unit setting value has to be
"Dimensionless", where the input range can be linearly scaled with the setting Input
minimum and Input maximum to Value minimum and Value maximum. When
resistance is used as an output unit, Value unit has to be "Ohm". When Value unit is
set to "Ohm", the linear scaling is not possible, but the default range (0...2000 Ω) can
be set smaller with the Value maximum and Value minimum settings.