ABB RELION 620 Series Technical Manual page 977

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MRS757644 F
620 series
Technical Manual
Table 949:
RDRE Non-group channel settings
Parameter
Values (Range) Unit
Operation
1=on
5=off
Channel
0=Disabled
selection
1=Io
2=IL1
3=IL2
4=IL3
5=IoB
6=IL1B
7=IL2B
8=IL3B
9=Uo
10=U1
11=U2
12=U3
14=U1B
17=CIo
18=SI1
1)
1)
19=SI2
20=SU0
21=SU1
1)
1)
22=SU2
23=CIoB
1)
24=SI1B
1)
25=SI2B
52=U1C
Channel id
0 to 64
text
characters,
alphanumeric
High trigger
0.00...60.00
level
Low trigger
0.00...2.00
level
Storage mode
0=Waveform
1=Trend /
cycle
1) Recordable values are available only in trend mode. In waveform mode, samples for this signal type are
constant zeroes. However, these signal types can be used to trigger the recorder on limit violations of
the corresponding analog channel.
Measurement functions
Step
1
0
pu
0.01
pu
0.01
1
Section 8
Default
Description
1=on
Analog
channel is
enabled or
disabled
0=Disabled
Select the
signal to be
recorded by
this channel.
Applicable
values for this
parameter are
product
variant
dependent.
Every product
variant
includes only
the values that
are applicable
to that
particular
variant
DR analog
Identification
channel X
text for the
analog
channel used
in the
COMTRADE
format
10.00
High trigger
level for the
analog
channel
0.00
Low trigger
level for the
analog
channel
0
Storage mode
for the analog
channel
971

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents