Setting Guidelines; Single Point Generic Control 8 Signals Spc8Gapc; Identification - ABB RES670 Applications Manual

Relion 670 series phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Section 14
Control
14.3.3
14.4
14.4.1
220
function block in which systems, equipment or functions should receive this
information.
More specifically, DPGAPC function reports a combined double point position
indication output POSITION, by evaluating the value and the timestamp attributes
of the inputs OPEN and CLOSE, together with the logical input signal VALID.
When the input signal VALID is active, the values of the OPEN and CLOSE inputs
determine the two-bit integer value of the output POSITION. The timestamp of the
output POSITION will have the latest updated timestamp of the inputs OPEN and
CLOSE.
When the input signal VALID is inactive, DPGAPC function forces the position to
intermediated state.
When the value of the input signal VALID changes, the timestamp of the output
POSITION will be updated as the time when DPGAPC function detects the
change.
Refer to Table
23
for the description of the input-output relationship in terms of the
value and the quality attributes.
Table 23:
Description of the input-output relationship
VALID
OPEN
0
-
1
0
1
1
1
0
1
1

Setting guidelines

The function does not have any parameters available in the local HMI or PCM600.

Single point generic control 8 signals SPC8GAPC

Identification

Function description
Single point generic control 8 signals
CLOSE
Value
-
0
0
0
0
1
1
2
1
3
IEC 61850
IEC 60617
identification
identification
SPC8GAPC
-
Phasor measurement unit RES670 2.2 IEC
1MRK 511 407-UEN C
POSITION
Description
Intermediate
Intermediate
Open
Closed
Bad State
SEMOD55398-5 v5
SEMOD176448-1 v3
SEMOD176456-2 v3
ANSI/IEEE C37.2
device number
-
Application manual

Advertisement

Table of Contents
loading

Table of Contents