ABB RELION 620 Series Technical Manual page 494

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 4
Protection functions
4.2.8.6
4.2.8.7
Table 470:
MFADPSDE Group settings (Basic)
Parameter
Directional mode
Voltage start value
Operate delay time
Table 471:
MFADPSDE Group settings (Advanced)
Parameter
Operating quantity
Min operate current
Tilt angle
Table 472:
MFADPSDE Non group settings (Basic)
Parameter
Operation
Operation mode
488
Signals
Table 468:
MFADPSDE Input signals
Name
Io
Uo
BLOCK
RELEASE
RESET
Table 469:
MFADPSDE Output signals
Name
OPERATE
START
BLK_EF
INTR_EF
PEAK_IND
Settings
Values (Range)
Unit
2=Forward
3=Reverse
0.01...1.00
xUn
60...1200000
ms
Values (Range)
Unit
1=Adaptive
2=Amplitude
0.005...5.000
xIn
2.0...20.0
deg
Values (Range)
Unit
1=on
5=off
1=Intermittent EF
3=General EF
4=Alarming EF
Type
Default
Description
SIGNAL
0
Residual current
SIGNAL
0
Residual voltage
BOOLEAN
0=False
Block signal for activating the blocking mode
BOOLEAN
0=False
External trigger to release neutral admittance
protection
BOOLEAN
0=False
External trigger to reset direction calculatio
Type
Description
BOOLEAN
Operate
BOOLEAN
Start
BOOLEAN
Block signal for EF to indicate opposite direction
peaks
BOOLEAN
Intermittent earth-fault indication
BOOLEAN
Current transient detection indication
Step
Default
2=Forward
0.01
0.10
10
500
Step
Default
1=Adaptive
0.001
0.010
0.1
5.0
Step
Default
1=on
3=General EF
1MRS757644 F
Description
Directional mode
Voltage start value
Operate delay time
Description
Operating quantity selection
Minimum operate current
Characteristic tilt angle
Description
Operation Off / On
Operation criteria
Technical Manual
620 series