ABB RELION 620 Series Technical Manual page 753

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MRS757644 F
4.8.3.7
Table 709:
DQPTUV Group settings (Basic)
Parameter
Values (Range)
Voltage start value
Operate delay time
Table 710:
DQPTUV Non group settings (Basic)
Parameter
Values (Range)
Operation
Table 711:
DQPTUV Non group settings (Advanced)
Parameter
Values (Range)
Min reactive power
Min Ps Seq current
Pwr sector reduction
Pol reversal
4.8.3.8
620 series
Technical Manual
Table 708:
DQPTUV Output signals
Name
OPERATE
START
Settings
Unit
0.20...1.20
xUn
100...300000
ms
Unit
1=on
5=off
Unit
0.01...0.50
xSn
0.02...0.20
xIn
0...10
deg
0=False
1=True
Monitored data
Table 712:
DQPTUV Monitored data
Name
START_DUR
Q
DQPTUV
Type
Description
BOOLEAN
Operate
BOOLEAN
Start
Step
Default
0.01
0.85
10
500
Step
Default
1=on
Step
Default
0.01
0.05
0.01
0.05
1
3
0=False
Type
Values (Range)
FLOAT32
0.00...100.00
FLOAT32
-160.000...160.0
00
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Section 4
Protection functions
Description
Start value for under voltage detection
Operate delay time
Description
Operation On/Off
Description
Minimum reactive power needed for
function to operate
Minimum positive sequence current
Power sector reduction
Reverse the definition of the positive
reactive power direction
Unit
Description
%
Ratio of start time /
operate time
xSn
Reactive power
Status
747