1MRS757644 F
Table 390:
EFHPTOC Non group settings (Advanced)
Parameter
Values (Range)
Minimum operate time
Reset delay time
Measurement mode
Io signal Sel
Table 391:
EFIPTOC Group settings (Basic)
Parameter
Values (Range)
Start value
Start value Mult
Operate delay time
Table 392:
EFIPTOC Non group settings (Basic)
Parameter
Values (Range)
Operation
Table 393:
EFIPTOC Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
Io signal Sel
4.2.1.10
620 series
Technical Manual
Unit
20...60000
ms
0...60000
ms
1=RMS
2=DFT
3=Peak-to-Peak
1=Measured Io
2=Calculated Io
Unit
1.00...40.00
xIn
0.8...10.0
20...200000
ms
Unit
1=on
5=off
Unit
0...60000
ms
1=Measured Io
2=Calculated Io

Monitored data

Table 394:
EFLPTOC Monitored data
Name
START_DUR
EFLPTOC
Step
Default
1
20
1
20
2=DFT
1=Measured Io
Step
Default
0.01
1.00
0.1
1.0
10
20
Step
Default
1=on
Step
Default
1
20
1=Measured Io
Type
Values (Range)
FLOAT32
0.00...100.00
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Section 4
Protection functions
Description
Minimum operate time for IDMT curves
Reset delay time
Selects used measurement mode
Selection for used Io signal
Description
Start value
Multiplier for scaling the start value
Operate delay time
Description
Operation Off / On
Description
Reset delay time
Selection for used Io signal
Unit
Description
%
Ratio of start time /
operate time
Status
369