Setting Guidelines; Single Point Generic Control 8 Signals Spc8Gapc; Identification; Application - ABB RELION 650 Series Applications Manual

Line differential protection version 2.1
Hide thumbs Also See for RELION 650 Series:
Table of Contents

Advertisement

1MRK 505 363-UEN A
manual, and define which function block in which systems, equipment or functions should
receive this information.
More specifically, DPGAPC function reports a combined double point position indication
output POSITION, by evaluating the value and the timestamp attributes of the inputs OPEN
and CLOSE, together with the logical input signal VALID.
When the input signal VALID is active, the values of the OPEN and CLOSE inputs determine the
two-bit integer value of the output POSITION. The timestamp of the output POSITION will have
the latest updated timestamp of the inputs OPEN and CLOSE.
When the input signal VALID is inactive, DPGAPC function forces the position to intermediated
state.
When the value of the input signal VALID changes, the timestamp of the output POSITION will
be updated as the time when DPGAPC function detects the change.
Refer to Table
the quality attributes.
Table 28: Description of the input-output relationship
VALID
0
12.6.3

Setting guidelines

The function does not have any parameters available in the local HMI or PCM600.
12.7

Single point generic control 8 signals SPC8GAPC

12.7.1

Identification

Function description
Single point generic control 8 signals
12.7.2

Application

The Single point generic control 8 signals (SPC8GAPC) function block is a collection of 8 single
point commands that can be used for direct commands for example reset of LED's or putting
IED in "ChangeLock" state from remote. In this way, simple commands can be sent directly to
the IED outputs, without confirmation. Confirmation (status) of the result of the commands is
supposed to be achieved by other means, such as binary inputs and SPGGIO function blocks.
Application manual
28
for the description of the input-output relationship in terms of the value and
OPEN
-
1
0
1
1
1
0
1
1
CLOSE
-
0
0
1
1
IEC 61850
IEC 60617
identification
identification
SPC8GAPC
-
POSITION
Value
Description
0
Intermediate
0
Intermediate
1
Open
2
Closed
3
Bad State
ANSI/IEEE C37.2
device number
-
Section 12
Control
SEMOD55398-5 v4
SEMOD176448-1 v3
SEMOD176456-2 v3
SEMOD176511-4 v5
245