Section 4
Protection functions
Table 587:
PHAPTOV Group settings (Advanced)
Parameter
Type of reset curve
Type of time reset
Table 588:
PHAPTOV Non group settings (Basic)
Parameter
Operation
Curve parameter A
Curve parameter B
Curve parameter C
Curve parameter D
Curve parameter E
Voltage selection
Table 589:
PHAPTOV Non group settings (Advanced)
Parameter
Minimum operate time
Reset delay time
Curve Sat Relative
Relative hysteresis
4.5.2.9
640
Values (Range)
Unit
1=Immediate
2=Def time reset
1=Freeze Op timer
2=Decrease Op
timer
Values (Range)
Unit
1=on
5=off
0.005...200.000
0.50...100.00
0.0...1.0
0.000...60.000
0.000...3.000
1=phase-to-earth
2=phase-to-phase
Values (Range)
Unit
40...60000
ms
0...60000
ms
0.0...3.0
1.0...5.0
%
Monitored data
Table 590:
PHAPTOV Monitored data
Name
START_DUR
PHAPTOV
Step
Default
1=Immediate
1=Freeze Op timer
Step
Default
1=on
1
1.000
1
1.00
1
0.0
1
0.000
1
1.000
2=phase-to-phase
Step
Default
1
40
1
20
0.1
2.0
0.1
4.0
Type
Values (Range)
FLOAT32
0.00...100.00
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
1MRS757644 F
Description
Selection of reset curve type
Selection of time reset
Description
Operation Off / On
Parameter A for customer programmable
curve
Parameter B for customer programmable
curve
Parameter C for customer programmable
curve
Parameter D for customer programmable
curve
Parameter E for customer programmable
curve
Parameter to select phase or phase-to-
phase voltages
Description
Minimum operate time for IDMT curves
Reset delay time
Tuning parameter to avoid curve
discontinuities
Relative hysteresis for operation
Unit
Description
%
Ratio of start time /
operate time
Status
Technical Manual
620 series