Technical data
Table 940:
VSMSQI Technical data
Characteristic
Operation accuracy
Suppression of harmonics
Three-phase power and energy measurement PEMMXU
Identification
Function description
Three-phase power and energy
measurement
Function block
GUID-E38A24DA-85CE-4246-9C3F-DFC6FDAEA302 V1 EN
Figure 499:
Function block
Signals
Table 941:
PEMMXU Input signals
Name
Type
I_A
SIGNAL
I_B
SIGNAL
I_C
SIGNAL
U_A
SIGNAL
U_B
SIGNAL
U_C
SIGNAL
RSTACM
BOOLEAN
Measurement functions
Value
Depending on the frequency of the voltage
measured: f
±2 Hz
n
At voltages in range 0.01...1.15 × U
±1.0% or ±0.002 × U
DFT: -50 dB at f = n × f
IEC 61850
IEC 60617
identification
identification
PEMMXU
P, E
Default
Description
0
Phase A current
0
Phase B current
0
Phase C current
0
Phase A voltage
0
Phase B voltage
0
Phase C voltage
0=False
Reset of accumulated energy reading
Section 8
n
n
, where n = 2, 3, 4, 5,...
n
ANSI/IEEE C37.2
device number
P, E
959