Figure 342:
Operating time curves for the overexcitation IDMT curve ("OvExt
IDMT Crv1") for parameters a = 2.5, b = 115.0 and c = 4.886
Overexcitation IDMT curve 4
The base equation for the IDMT curve "OvExt IDMT Crv4" is:
d
0 18
.
k
t s
( )
=
+
2
1000
(
M
1
)
GUID-E9F10438-C3F2-4440-AB4B-32C2EB17CF72 V1 EN
t(s) Operate time in seconds
Constant delay setting in seconds
d
M
Excitation value (U/f ratio or volts/hertz) in pu
Time multiplier setting
k
Section 4
Protection functions
(Equation 135)