Figure 156:
Effective start value for voltage step characteristic
The voltage slope characteristic is achieved by assigning different values to Voltage
high limit and Voltage low limit. The effective start value calculation is based on the
equations.
Voltage level
U <
Voltage low limit
Voltage high limit
U ≥
If Voltage low limit ≤ U < Voltage high limit,
A- I >
I > (effective)=A -
C - D
GUID-ABAAC011-1BC7-4606-AE60-FEC25E6CE155 V1 EN
A
set
Start value low
Start value
I> set
C
set
Voltage high limit
Voltage low limit
D
set
Here U represents the measured input voltage. The voltage slope characteristic is
graphically represented.
Effective start value (I> effective)
Start value low
Start value
(C -U)
 ⋅
Section 4
Protection functions
(Equation 7)
311