Section 6
Supervision functions
6.4.8
Table 856:
HZCCASPVC Non group settings (Basic)
Parameter
Operation
Start value
Alarm delay time
Alarm output mode
Table 857:
HZCCASPVC Non group settings (Advanced)
Parameter
Reset delay time
Measurement mode
Table 858:
HZCCBSPVC Non group settings (Basic)
Parameter
Operation
Start value
Alarm delay time
Alarm output mode
Table 859:
HZCCBSPVC Non group settings (Advanced)
Parameter
Reset delay time
Measurement mode
896
Table 855:
HZCCCSPVC Output signals
Name
ALARM
Settings
Values (Range)
Unit
1=on
5=off
1.0...100.0
%In
100...300000
ms
1=Non-latched
3=Lockout
Values (Range)
Unit
0...60000
ms
2=DFT
3=Peak-to-Peak
Values (Range)
Unit
1=on
5=off
1.0...100.0
%In
100...300000
ms
1=Non-latched
3=Lockout
Values (Range)
Unit
0...60000
ms
2=DFT
3=Peak-to-Peak
Type
Description
BOOLEAN
Alarm output
Step
Default
1=on
0.1
10.0
10
3000
3=Lockout
Step
Default
10
20
2=DFT
Step
Default
1=on
0.1
10.0
10
3000
3=Lockout
Step
Default
10
20
2=DFT
1MRS757644 F
Description
Operation Off / On
Start value, percentage of the nominal
current
Alarm delay time
Select the operation mode for alarm
output
Description
Reset delay time
Selects used measurement mode
Description
Operation Off / On
Start value, percentage of the nominal
current
Alarm delay time
Select the operation mode for alarm
output
Description
Reset delay time
Selects used measurement mode