Length Of Record - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MRS757644 F
3.19.2.2
620 series
Technical Manual
Disabled
Quantity not selected
U12
Phase-to-phase 12 voltage
U23
Phase-to-phase 23 voltage
U31
Phase-to-phase 31 voltage
UL1
Phase-to-earth 1 voltage
UL2
Phase-to-earth 2 voltage
UL3
Phase-to-earth 3 voltage
UL1B
Phase-to-earth 1 voltage, B side
UL2B
Phase-to-earth 2 voltage, B side
UL3B
Phase-to-earth 3 voltage, B side
S
Apparent power
P
Real power
Q
Reactive power
PF
Power factor
If the data source for the selected quantity is removed, for example,
with Application Configuration in PCM600, the load profile recorder
stops recording it and the previously collected data are cleared.

Length of record

The recording capability is about 7.4 years when one quantity is recorded and the
demand interval is set to 180 minutes. The recording time scales down proportionally
when a shorter demand time is selected or more quantities are recorded. The recording
lengths in days with different settings used are presented in
recording buffer is fully occupied, the oldest data are overwritten by the newest data.
Table 207:
Recording capability in days with different settings
1
5
minute
minutes
Amount of
quantities
1
15.2
75.8
2
11.4
56.9
3
9.1
45.5
4
7.6
37.9
5
6.5
32.5
6
5.7
28.4
7
5.1
25.3
8
4.5
22.7
Table continues on next page
Demand interval
10
15
minutes
minutes
minutes
Recording capability in days
151.6
227.4
454.9
113.7
170.6
341.1
91.0
136.5
272.9
75.8
113.7
227.4
65.0
97.5
194.9
56.9
85.3
170.6
50.5
75.8
151.6
45.5
68.2
136.5
Section 3
Basic functions
Table
207. When the
30
60
180
minutes
minutes
909.7
2729.2
682.3
2046.9
545.8
1637.5
454.9
1364.6
389.9
1169.6
341.1
1023.4
303.2
909.7
272.9
818.8
203

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents