Section 5
Protection related functions
5.1.6
5.1.7
Table 769:
INRPHAR Group settings (Basic)
Parameter
Start value
Operate delay time
Table 770:
INRPHAR Non group settings (Basic)
Parameter
Operation
Table 771:
INRPHAR Non group settings (Advanced)
Parameter
Reset delay time
5.1.8
806
Signals
Table 767:
INRPHAR Input signals
Name
I_2H_A
I_1H_A
I_2H_B
I_1H_B
I_2H_C
I_1H_C
BLOCK
Table 768:
INRPHAR Output signals
Name
BLK2H
Settings
Values (Range)
Unit
5...100
%
20...60000
ms
Values (Range)
Unit
1=on
5=off
Values (Range)
Unit
0...60000
ms
Monitored data
Table 772:
INRPHAR Monitored data
Name
INRPHAR
Type
Default
Description
SIGNAL
0
Second harmonic phase A current
SIGNAL
0
Fundamental frequency phase A current
SIGNAL
0
Second harmonic phase B current
SIGNAL
0
Fundamental frequency phase B current
SIGNAL
0
Second harmonic phase C current
SIGNAL
0
Fundamental frequency phase C current
BOOLEAN
0=False
Block input status
Type
Description
BOOLEAN
Second harmonic based block
Step
Default
1
20
1
20
Step
Default
1=on
Step
Default
1
20
Type
Values (Range)
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
1MRS757644 F
Description
Ratio of the 2. to the 1. harmonic leading
to restraint
Operate delay time
Description
Operation Off / On
Description
Reset delay time
Unit
Description
Status
Technical Manual