1MRS757644 F
4.12.2.2
4.12.2.3
4.12.2.4
620 series
Technical Manual
Function block
GUID-6447040F-55DC-4FA5-9111-0941695F8544 V1 EN
Figure 400:
Function block symbol
Functionality
The current unbalance protection for shunt capacitor banks function CUBPTOC is
used to protect the double-Y-connected capacitor banks from internal faults.
CUBPTOC is suitable for the protection of internally fused, externally fused and
fuseless applications.
CUBPTOC has two stages of operation, that is, operation stage and alarm stage. In the
operating stage, CUBPTOC starts when the measured unbalance current exceeds the
set limit. The operation time characteristics can be selected to be either definite time
(DT) or inverse definite minimum time (IDMT). The operation under alarm stage is
either based on the DT characteristics or the faulty element counter of a capacitor
bank.
CUBPTOC has a blocking functionality. It is possible to block the function outputs,
timers or the function itself, if required.
Operation principle
The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "On" and "Off". The current unbalance
protection for shunt capacitor banks operates on the DFT measurement mode.
The operation of CUBPTOC can be described by using a module diagram. All the
modules in the diagram are explained in the next sections.
Section 4
Protection functions
783