Table 796:
ESMGAPC Group settings (Advanced)
Parameter
Values (Range)
Motor standstill A
Table 797:
ESMGAPC Non group settings (Basic)
Parameter
Values (Range)
Operation
620 series
Technical Manual
Application
If the motor needs to be started in an emergency condition at the risk of damaging the
motor, all the external restart inhibits are ignored, allowing the motor to be restarted.
Furthermore, if the calculated thermal level is higher than the restart inhibit level at an
emergency start condition, the calculated thermal level is set slightly below the restart
inhibit level. Also, if the register value of the cumulative start-up time counter exceeds
the restart inhibit level, the value is set slightly below the restart disable value to allow
at least one motor start-up.
The activation of the ST_EMERG_RQ digital input allows to perform emergency start.
The protection relay is forced to a state which allows the restart of motor, and the
operator can now restart the motor. A new emergency start cannot be made until the
10 minute time-out has passed or until the emergency start is released, whichever
takes longer.
The last change of the emergency start output signal is recorded.
Signals
Table 794:
ESMGAPC Input signals
Name
I_A
I_B
I_C
BLOCK
ST_EMERG_RQ
Table 795:
ESMGAPC Output signals
Name
ST_EMERG_ENA
Settings
Unit
0.05...0.20
xIn
Unit
1=on
5=off
Type
Default
Description
SIGNAL
0
Phase A current
SIGNAL
0
Phase B current
SIGNAL
0
Phase C current
BOOLEAN
0=False
Block signal for activating the blocking mode
BOOLEAN
0=False
Emergency start input
Type
Description
BOOLEAN
Emergency start
Step
Default
0.01
0.12
Step
Default
1=on
Protection related functions
Description
Current limit to check for motor standstill
condition
Description
Operation Off / On
Section 5
829