Section 4
Protection functions
4.3.5.10
4.3.5.11
588
Table 526:
HIBPDIF Monitored data
Name
Type
START_DUR
FLOAT32
HIBPDIF
Enum
Table 527:
HICPDIF Monitored data
Name
Type
START_DUR
FLOAT32
HICPDIF
Enum
Technical data
Table 528:
HIxPDIF Technical data
Characteristic
Operation accuracy
Start time
1)2)
I
Fault
value
I
Fault
value
Reset time
Reset ratio
Retardation time
Operate time accuracy in definite time mode
Measurement mode = default (depends on stage), current before fault = 0.0 × I
1)
with nominal frequency injected from random phase angle, results based on statistical distribution of
1000 measurements
2) Includes the delay of the signal output contact
Technical revision history
Table 529:
HIxPDIF Technical revision history
Technical revision
B
Values (Range)
Unit
0.00...100.00
%
1=on
2=blocked
3=test
4=test/blocked
5=off
Values (Range)
Unit
0.00...100.00
%
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
Depending on the frequency of the current
measured: f
±1.5% of the set value or ±0.002 × I
Minimum
Start
= 2.0 × set
12 ms
Start
= 10 × set
10 ms
<40 ms
Typically 0.96
<35 ms
±1.0% of the set value or ±20 ms
Change
Function name changed from HIPDIF to HIAPDIF,
HIBPDIF, HICPDIF
1MRS757644 F
Description
Ratio of start time /
operate time
Status
Description
Ratio of start time /
operate time
Status
±2 Hz
n
n
Typical
Maximum
16 ms
24 ms
12 ms
14 ms
, f
= 50 Hz, fault current
n
n
620 series
Technical Manual