ABB RELION 620 Series Technical Manual page 690

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 4
Protection functions
4.5.8.8
Table 642:
OEPVPH Group settings (Basic)
Parameter
Start value
Operating curve type
Time multiplier
Operate delay time
Table 643:
OEPVPH Non group settings (Basic)
Parameter
Operation
Cooling time
Constant delay
Maximum operate time
Voltage selection
Table continues on next page
684
Name
U
1
F
BLOCK
Table 641:
OEPVPH Output signals
Name
OPERATE
START
BLK_RESTART
COOL_ACTIVE
Settings
Values (Range)
Unit
100...200
%
5=ANSI Def. Time
15=IEC Def. Time
17=OvExt IDMT
Crv1
18=OvExt IDMT
Crv2
19=OvExt IDMT
Crv3
20=OvExt IDMT
Crv4
0.1...100.0
200...200000
ms
Values (Range)
Unit
1=on
5=off
5...10000
s
100...120000
ms
500000...10000000
ms
1=phase-to-earth
2=phase-to-phase
3=pos sequence
Type
Default
Description
SIGNAL
0
Positive-phase sequence voltage
SIGNAL
0
Measured frequency
BOOLEAN
0=False
Block signal
Type
Description
BOOLEAN
Operated
BOOLEAN
Started
BOOLEAN
Signal for blocking reconnection of an overheated
machine
BOOLEAN
Signal to indicate machine is in cooling process
Step
Default
1
100
15=IEC Def. Time
0.1
3.0
10
500
Step
Default
1=on
1
600
10
800
10
1000000
3=pos sequence
1MRS757644 F
Description
Over excitation start value
Selection of time delay curve type
Time multiplier for Overexcitation IDMT
curves
Operate delay time in definite- time mode
Description
Operation Mode Off / On
Time required to cool the machine
Parameter constant delay
Maximum operate time for IDMT curves
Selection of phase / phase-to-phase / pos
sequence voltages
Technical Manual
620 series