Signals; Settings; Monitored Data - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MRS757644 F
3.17.15.5
3.17.15.6
Table 204:
UDFCNT Non group settings (Basic)
Parameter
Values (Range)
Operation
Counter load value
Reset counter
Load counter
3.17.15.7
620 series
Technical Manual
Input 1 filter time is set to "5...15 ms" via Configuration/I/O modules/
X110(BIO)/Input filtering
Input osc. level is set to "45...50 events/s" via Configuration/I/O modules/
Common settings
Input osc. hyst is set to "2 events/s" via Configuration/I/O modules/Common

settings

Signals

Table 202:
UDFCNT Input signals
Name
UP_CNT
DOWN_CNT
RESET
LOAD
Table 203:
UDFCNT Output signals
Name
UPCNT_STS
DNCNT_STS
Settings
Unit
1=on
5=off
0...2147483647
0=Cancel
1=Reset
0=Cancel
1=Load

Monitored data

Table 205:
UDFCNT Monitored data
Name
CNT_VAL
Type
Default
Description
BOOLEAN
0=False
Input for up counting
BOOLEAN
0=False
Input for down counting
BOOLEAN
0=False
Reset input for counter
BOOLEAN
0=False
Load input for counter
Type
Description
BOOLEAN
Status of the up counting
BOOLEAN
Status of the down counting
Step
Default
1=on
1
10000
0=Cancel
0=Cancel
Type
Values (Range)
INT64
0...2147483647
Section 3
Basic functions
Description
Operation Off / On
Preset counter value
Resets counter value
Loads the counter to preset value
Unit
Description
Output counter value
201