Monitored Data - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MRS757644 F
Table 261:
PH3HPTOC Non group settings (Advanced)
Parameter
Values (Range)
Minimum operate time
Reset delay time
Measurement mode
Table 262:
PH3IPTOC Group settings (Basic)
Parameter
Values (Range)
Start value
Start value Mult
Operate delay time
Table 263:
PH3IPTOC Non group settings (Basic)
Parameter
Values (Range)
Operation
Num of start phases
Table 264:
PH3IPTOC Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
4.1.2.9
620 series
Technical Manual
Unit
20...60000
ms
0...60000
ms
1=RMS
2=DFT
3=Peak-to-Peak
Unit
1.00...40.00
xIn
0.8...10.0
20...200000
ms
Unit
1=on
5=off
1=1 out of 3
2=2 out of 3
3=3 out of 3
Unit
0...60000
ms

Monitored data

Table 265:
PH3LPTOC Monitored data
Name
START_DUR
PH3LPTOC
Step
Default
10
20
10
20
2=DFT
Step
Default
0.01
1.00
0.1
1.0
10
20
Step
Default
1=on
1=1 out of 3
Step
Default
10
20
Type
Values (Range)
FLOAT32
0.00...100.00
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Section 4
Protection functions
Description
Minimum operate time for IDMT curves
Reset delay time
Selects used measurement mode
Description
Start value
Multiplier for scaling the start value
Operate delay time
Description
Operation Off / On
Number of phases required for operate
activation
Description
Reset delay time
Unit
Description
%
Ratio of start time /
operate time
Status
257