ABB RELION 620 Series Technical Manual page 747

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MRS757644 F
4.8.2.6
4.8.2.7
Table 702:
DOPPDPR Group settings (Basic)
Parameter
Values (Range)
Start value
Operate delay time
Directional mode
Power angle
Table 703:
DOPPDPR Non group settings (Basic)
Parameter
Values (Range)
Operation
Measurement mode
620 series
Technical Manual
Signals
Table 700:
DOPPDPR Input signals
Name
I_A
I_B
I_C
U_A_AB
U_A_BC
U_A_CA
BLOCK
Table 701:
DOPPDPR Output signals
Name
OPERATE
START
Settings
Unit
0.01...2.00
xSn
40...300000
ms
2=Forward
3=Reverse
-90...90
deg
Unit
1=on
5=off
1=PhsA, PhsB,
PhsC
2=Arone
3=Pos Seq
4=PhsAB
5=PhsBC
6=PhsCA
7=PhsA
8=PhsB
9=PhsC
Type
Default
Description
SIGNAL
0
Phase A current
SIGNAL
0
Phase B current
SIGNAL
0
Phase C current
SIGNAL
0
Phase-to-earth voltage A or phase-to-phase
voltage AB
SIGNAL
0
Phase-to-earth voltage B or phase-to-phase
voltage BC
SIGNAL
0
Phase-to-earth voltage C or phase-to-phase
voltage CA
BOOLEAN
0=False
Block signal for activating the blocking mode
Type
Description
BOOLEAN
Operate
BOOLEAN
Start
Step
Default
0.01
1.00
10
40
2=Forward
1
0
Step
Default
1=on
3=Pos Seq
Section 4
Protection functions
Description
Start value
Operate delay time
Directional mode
Adjustable angle for power
Description
Operation On/Off
Selection of power calculation method
741

Hide quick links:

Advertisement

Table of Contents
loading