ABB RELION 620 Series Technical Manual page 961

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MRS757644 F
8.1.10.6
620 series
Technical Manual
Name
Type
I2_DB
FLOAT32
I2_RANGE
Enum
I1_INST
FLOAT32
I1_ANGL
FLOAT32
I1_DB
FLOAT32
I1_RANGE
Enum
I0_INST
FLOAT32
I0_ANGL
FLOAT32
I0_DB
FLOAT32
I0_RANGE
Enum
Technical data
Table 935:
CSMSQI Technical data
Characteristic
Operation accuracy
Suppression of harmonics
Measurement functions
Values (Range)
Unit
0.00...40.00
xIn
0=normal
1=high
2=low
3=high-high
4=low-low
0.00...40.00
xIn
-180.00...180.00
deg
0.00...40.00
xIn
0=normal
1=high
2=low
3=high-high
4=low-low
0.00...40.00
xIn
-180.00...180.00
deg
0.00...40.00
xIn
0=normal
1=high
2=low
3=high-high
4=low-low
Value
Depending on the frequency of the measured
current: f/f
= ±2 Hz
n
±1.0% or ±0.002 × I
at currents in the range of 0.01...4.00 × I
DFT: -50 dB at f = n × f
Section 8
Description
Negative sequence
current amplitude,
reported value
Negative sequence
current amplitude range
Positive sequence
current amplitude,
instantaneous value
Positive sequence
current angle
Positive sequence
current amplitude,
reported value
Positive sequence
current amplitude range
Zero sequence current
amplitude, instantaneous
value
Zero sequence current
angle
Zero sequence current
amplitude, reported value
Zero sequence current
amplitude range
n
n
, where n = 2, 3, 4, 5,...
n
955